Indoor air quality monitoring in office buildings to investigate employee complaints about stuffy air, headaches and workplace air quality.

Indoor Air Quality Monitoring: Investigating Complaints in Office Building

An employee reports headaches and stuffy air in a meeting room. Another team notices an unusual odour on a different floor. The facility manager checks the HVAC system, which appears to operate normally.

But the complaints continue.

By the time a facility team inspects the affected space, the conditions that prompted the complaint may have already changed.

Indoor air quality monitoring helps connect occupant feedback with environmental conditions and building operations. To investigate indoor air quality complaints in offices, document where and when concerns occur, inspect ventilation and potential sources, measure relevant parameters, and compare findings with occupancy and operating records. Then verify whether corrective action resolves the complaint.

Listen The Blog

Listen the blog in 60 sec​

Why Office Air Quality Complaints

Need a Structured Investigation

Six-step indoor air quality monitoring process for office buildings, from documenting complaints and inspecting ventilation to measuring IAQ parameters, correcting issues and verifying improvements.

Office buildings contain different ventilation zones, occupancy patterns and potential pollution sources. A conference room may become uncomfortable during meetings while neighbouring workspaces remain unaffected.

Intermittent complaints create another difficulty. A spot check after occupants leave may miss the conditions that prompted the report.

Indian workplace research reflects the importance of considering both building conditions and occupant experiences. A joint study by GBCI India and Saint-Gobain Research India assessed 30 offices across nine cities, using environmental measurements, building inspections, building information and occupant surveys.

The study highlights why facility teams need to consider multiple sources of information when investigating indoor air quality. A sensor reading can indicate a change in CO₂, particulate matter or temperature, but it does not explain what caused that change or how it relates to occupant complaints. Information about occupancy, building operations and occupant feedback helps put these readings into context.

Facility teams can use this approach to move from occupant complaints to a closer examination of the building conditions behind them.

1) Document Office Air Quality Complaints and Their Timing

Start with a consistent complaint record before changing system settings. Capture:

  • Location: Floor, room, workstation and nearby activities.
  • Timing: When the problem starts, its duration and recurrence.
  • Experience: Odour, stuffiness, irritation, temperature discomfort or reported symptoms.
  • Occupancy: People present and activities taking place.
  • Recent changes: Cleaning, pest control, fit-outs, furniture installation or maintenance.

Ask whether the concern improves when the person leaves the space. Mark affected locations on a floor plan and identify the HVAC zones serving them.

Several complaints within one ventilation zone suggest a different investigation from an isolated report beside a pantry.

Assign a response owner and explain the next steps to occupants. 

2. Inspect Ventilation Systems and Potential Indoor Pollution Sources

Visit the affected area while occupants are experiencing the problem, where possible. Speak with occupants, housekeeping staff and maintenance personnel.

Check for blocked diffusers, obstructed return grilles, damp materials, water stains, poorly stored chemicals and recent renovation. Inspect outdoor air intakes for nearby vehicle exhaust, waste areas or other pollution sources.

Compare operating schedules with actual occupancy. A meeting room may remain in use after ventilation switches to reduced operation. New partitions may alter airflow without corresponding HVAC adjustments.

Shift-based workplaces face additional scheduling challenges, as discussed in our guide to indoor air quality monitoring for GCCs in India.

The US Environmental Protection Agency (EPA) provides guidance on investigating indoor air quality in buildings. Its Building Air Quality Guide recommends examining occupants, HVAC systems, pollutant sources and the pathways through which pollutants move.

For facility teams, this means looking beyond HVAC equipment and checking how outdoor pollutants, indoor activities and ventilation patterns may affect the space. These checks help narrow down possible causes and identify where further investigation is needed.

Record obvious defects and any immediate corrective work.

3. Select Indoor Air Quality Monitoring Parameters Based on the Complaint

The parameters selected for monitoring should reflect the complaints and conditions observed during the inspection. For instance, stuffy rooms may warrant examining CO₂ levels and ventilation, while reports of dust or unusual odours may require looking at particulate matter or VOCs.

Some commonly monitored parameters and what they help investigate include:

Parameter What It Helps Investigate
CO₂ Occupancy-related changes and whether outdoor air delivery needs assessment.
PM2.5 and PM10 Particulate increases, outdoor pollution ingress, indoor dust and filtration performance.
TVOC Changes that warrant examining cleaning products, furnishings or other emitting materials.
Temperature Uneven cooling, overheating and thermal discomfort.
Relative Humidity Moisture conditions and areas requiring inspection for dampness.

CO₂ readings can help assess ventilation, but they should not be treated as a standalone measure of indoor air quality. The US Centers for Disease Control and Prevention (CDC), through its National Institute for Occupational Safety and Health (NIOSH), cautions against applying a single CO₂ target across all room types and occupancy conditions. 

TVOC readings can flag changes in volatile compounds in the air, but they do not identify individual chemicals or establish their health risks. If a particular contaminant is suspected, targeted testing may be necessary.

Pay attention to monitor maintenance, placement and timestamps as well. Measurements should represent actual occupied conditions, rather than air directly from a diffuser or someone’s exhaled breath.

4. Compare Indoor Air Quality Across Rooms and Operating Periods

For intermittent office air quality complaints, compare conditions across both space and time.

Review the affected room alongside a nearby area without complaints. Include occupied periods, HVAC start-up and shutdown, cleaning schedules and other relevant activities.

Suppose CO₂ repeatedly rises during afternoon meetings while neighbouring workspaces remain stable. This gives the facility team a reason to examine that room’s occupancy, outdoor airflow and controls.

For particulate concerns, compare indoor and outdoor PM2.5 over the same period. Similar trends may justify checking intake filtration, entrances and building leakage. An isolated indoor increase warrants closer inspection of local activities.

5. Address the Causes of Office Air Quality Problems

For intermittent office air quality complaints, compare conditions across both space and time.

Review ta

Review monitoring trends alongside Building Management System (BMS) logs, maintenance records and airflow measurements. An HVAC unit showing as operational does not necessarily mean that every occupied space receives adequate outdoor air.

Check damper operation, filter condition, exhaust systems and ventilation settings. Depending on the findings, corrective work may involve repairing ventilation faults, addressing moisture ingress, removing pollution sources or improving filtration. Where necessary, involve a ventilation specialist to assess airflow against applicable design requirements.

During periods of high outdoor pollution, also consider how ventilation and particle filtration work together. Air cleaners can reduce airborne particles but cannot replace outdoor air ventilation for managing occupant-generated CO₂.

Record the corrective work, the person responsible and when the results will be reviewed.

6. Check Whether Corrective Action Resolved the Complaint

Compare conditions before and after corrective work under reasonably similar occupancy and operating conditions.

After a ventilation adjustment, review comparable meeting periods. Following filtration work, examine indoor particulate trends alongside outdoor pollution. Otherwise, cleaner outdoor conditions could create a misleading impression of improvement.

Ask affected occupants whether the original concern persists. If measurements improve but complaints continue, reassess the explanation and consider specialist assistance.

EPA guidance includes follow-up evaluation when determining whether an IAQ problem has been resolved. Completing maintenance alone does not demonstrate success.

Keep a closure record covering the findings, corrective work and follow-up results.

How Aurassure IAQMS Connects

Indoor Air Quality Monitoring with Building Response

Aurassure IAQMS indoor air quality monitoring dashboard displaying CO₂, PM2.5, PM10, TVOC, temperature, humidity, HVAC integration and office air quality alerts.

Resolving office air quality complaints requires a connection between the conditions employees report, the evidence facility teams collect and the actions they take.

Aurassure’s Indoor Air Quality Management System (IAQMS) brings continuous measurements, analytics and compatible building controls into one platform. It helps teams investigate recurring concerns, coordinate responses and assess whether conditions improve.

Facility teams can use IAQMS to:

  • Monitor occupied spaces: Track PM2.5, PM10, CO₂, TVOC, temperature and humidity across meeting rooms, work areas and other monitored zones.
  • Investigate recurring patterns: Compare historical trends across locations and complaint periods to identify where further inspection or operational changes are needed.
  • Direct attention through alerts: Notify responsible teams through app, email or SMS when measurements cross configured thresholds.
  • Connect findings with building response: Integrate with compatible BMS, HVAC and purification systems to enable configured ventilation adjustments or filtration and purification triggers.
  • Evaluate and document improvements: Review measurements after corrective work and export records for maintenance reviews, internal reporting and environmental performance assessments.

Control strategies should reflect the building’s ventilation requirements, outdoor air conditions and available treatment equipment. With suitable integration and commissioning, IAQMS connects detection, response and verification, giving facility teams a practical basis for managing indoor air quality as conditions change.

Explore Aurassure IAQMS to see how continuous monitoring, analytics and integrated controls can help your team investigate complaints and manage office air quality.

Conclusion: Using Indoor Air Quality Monitoring to

Prevent Recurring Complaints

Modern office workspace with employees and HVAC ventilation, illustrating how indoor air quality monitoring and investigation findings help prevent recurring workplace air quality complaints.

Recurring complaints can reveal gaps between building settings and actual workplace use. Carry investigation findings into maintenance schedules, occupancy planning, fit-out reviews and control settings.

A room that repeatedly exceeds its intended occupancy needs an operating decision. A recurring cleaning-related concern needs a review of products, methods or timing.

Effective indoor air quality management turns those findings into lasting changes. Each investigation should leave the facility team with a clearer understanding of the building and a defined response if the problem returns.

Air quality monitoring involves the continuous measurement of key air pollutants, often referred to as "criteria air pollutants." By analyzing air pollution data alongside natural background levels, trace gas monitoring, and emissions from stationary sources, Aurassure helps determine the type and extent of air pollution that people are exposed to.

Download the complete blog as a PDF

Mrinali Behera

Author

Mrinali Behera

Soumyajyoti Smrutisagar

Designer

Soumyajyoti

Sustainability Starts with You

Act Now for a Better Tomorrow
Ensure Regulatory Compliance​

Thank You!

Explore more insights and resources

on our website.

Indoor Air Quality Management System

Download Our Brochure Now

Get detailed insights into how Aurassure IAQMS improves air quality, reduces energy costs, and ensures compliance.

icon

We appreciate your feedback and will use it to improve our products and services. 

If you have any immediate concerns, 

please contact our customer success team (+91 90780 32911).

Contact Aurassure

Fill out the form below, and we will be in touch shortly.
Details Regarding